Experimental Investigation of the Temperature Distribution along the Two-Phase Thermosyphon Height and the Condensation Type on the Top Cover

Bibliographic Details
Parent link:AIP Conference Proceedings
Vol. 2337 : Thermophysical Basis of Energy Technologies (TBET 2020).— 2021.— [020020, 4 p.]
Main Author: Ponomarev K. O. Konstantin Olegovich
Corporate Author: Национальный исследовательский Томский политехнический университет Инженерная школа энергетики Научно-образовательный центр И. Н. Бутакова (НОЦ И. Н. Бутакова)
Other Authors: Abedtazehabadi A. Akram
Summary:Title screen
The temperature distribution along the thermosyphon height was experimentally established under the conditions of supplying the heat flow to the lower cover, which is typical of the operation of electronic equipment. It is shown that the drop condensation occurs on the condenser upper cover at heat flux of up to 1.8 kW/m2 on the lower cover of the thermosyphon evaporator. However, when the heat flux is in the range from 1.8 to 5.1 kW/m2, the drop-film condensation occurs.
Режим доступа: по договору с организацией-держателем ресурса
Published: 2021
Series:Technical thermal physics and nuclear energy
Subjects:
Online Access:https://doi.org/10.1063/5.0046465
Format: Electronic Book Chapter
KOHA link:https://koha.lib.tpu.ru/cgi-bin/koha/opac-detail.pl?biblionumber=664428