Improving the Efficiency of the Condensing Unit

Podrobná bibliografie
Parent link:AIP Conference Proceedings
Vol. 2212 : Thermophysical Basis of Energy Technologies (TBET 2019).— 2020.— [020047, 5 p.]
Hlavní autor: Popov D. V.
Korporativní autor: Национальный исследовательский Томский политехнический университет Инженерная школа энергетики Научно-образовательный центр И. Н. Бутакова (НОЦ И. Н. Бутакова)
Další autoři: Lavrinenko S. V. Sergey Viktorovich
Shrnutí:Title screen
The paper describes the characteristics of the evaporative cooling tower (ECT) of the third power unit of the Rostov NPP. The actual temperature of the circulating water at the power is determined. Actual temperature exceeds the design temperature by 5.27 C. During the visual inspection, the reasons for the temperature increase were identified: leaks through the butt joints of the pipelines, damage to the irrigation blocks and the uneven operation of the spray devices. Repair work did not solve the problem of limiting the electric power of the turbine unit. In this regard, a project was developed to modernize the power unit cooling system.
Режим доступа: по договору с организацией-держателем ресурса
Vydáno: 2020
Témata:
On-line přístup:https://doi.org/10.1063/5.0001266