HVDC LCC technology and power quality issues in cross-border electrical power transmission Russia - Finland; Innovative Smart Grid Technologies Conference Europe (ISGT Europe), IEEE PES

Dades bibliogràfiques
Parent link:Innovative Smart Grid Technologies Conference Europe (ISGT Europe), IEEE PES.— 2018.— [18345404, 6 p.]
Autor corporatiu: Национальный исследовательский Томский политехнический университет Инженерная школа энергетики Отделение электроэнергетики и электротехники (ОЭЭ)
Altres autors: Zmaznov E. Yu. Evgeny Yurjevich, Lozinova N. G., Suslova O. V., Andreev M. V. Mikhail Vladimirovich, Ufa R. A. Ruslan Alexandrovich, Ruban N. Yu. Nikolay Yurievich, Suvorov A. A. Aleksey Aleksandrovich
Sumari:Title screen
The results of field and theoretical studies of the harmonic interaction between two powerful converter substations Vyborgskaya and Rauma in MIDC system are described. It is shown that harmonic currents which are not filtered properly at one converter substation can propagate over the power network and be amplified at distant converter substation. In particular, the commissioning of the HVDC power transmission Fenno-Scan has affected the current psophometric value in 400 kV AC power system adjacent to Vyborgskaya back-to-back. The efficiency of a two-level harmonic filtration system is compared with a single-level system. Method of the propagation of harmonic currents in a network based on the network frequency characteristics is used. The paper also describes the influence of the 150 Hz corona harmonic current on the substation equipment.
Режим доступа: по договору с организацией-держателем ресурса
Idioma:anglès
Publicat: 2018
Matèries:
Accés en línia:https://doi.org/10.1109/ISGTEurope.2018.8571805
Format: Electrònic Capítol de llibre
KOHA link:https://koha.lib.tpu.ru/cgi-bin/koha/opac-detail.pl?biblionumber=664414

Ítems similars