Transformation of zero-sequence electric quantities for protection against line-to-ground fault in the networks with various neutral grounding modes; Industrial Engineering, Applications and Manufacturing (ICIEAM)

Dettagli Bibliografici
Parent link:Industrial Engineering, Applications and Manufacturing (ICIEAM).— 2016.— [5 p.]
Autore principale: Pashkovskiy S. N. Sergey Nikolaevich
Ente Autore: Национальный исследовательский Томский политехнический университет (ТПУ) Энергетический институт (ЭНИН) Кафедра электроэнергетических систем (ЭЭС)
Altri autori: Weinstein (Vaynshteyn) R. A. Robert Aleksandrovich, Yudin S. M. Svyatoslav Mikhaylovich
Riassunto:Title screen
The authors of the given article offer a diagram of an inlet part of protection against line-to-ground fault. The article deals with justification of its parameters, at which linear connection on mean values between the signal at protection outlet and input zero-sequence current, both by persistent and arcing intermittent faults, is provided. The article also describes the parameters ensuring thermal stability of protection by double triggering current. Time signal parameters at diagram output are compatible with the characteristics of analog-digital converters used in microprocessor units of relay protection. This diagram can be used for protection against line-to-ground faults in the networks with different neutral grounding modes.
Режим доступа: по договору с организацией-держателем ресурса
Lingua:inglese
Pubblicazione: 2016
Soggetti:
Accesso online:https://doi.org/10.1109/ICIEAM.2016.7911484
Natura: Elettronico Capitolo di libro
KOHA link:https://koha.lib.tpu.ru/cgi-bin/koha/opac-detail.pl?biblionumber=655234

Documenti analoghi