Conditions and Characteristics of Water Crystallization on the Working Surface of Evaporator Heat Pumps in Reservoirs with Low Temperatures; MATEC Web of Conferences; Vol. 23 : Heat and Mass Transfer in the Thermal Control System of Technical and Technological Energy Equipment

Մատենագիտական մանրամասներ
Parent link:MATEC Web of Conferences
Vol. 23 : Heat and Mass Transfer in the Thermal Control System of Technical and Technological Energy Equipment.— 2015.— [01051, 8 p.]
Հիմնական հեղինակ: Maksimov V. I. Vyacheslav Ivanovich
Համատեղ հեղինակ: Национальный исследовательский Томский политехнический университет (ТПУ) Энергетический институт (ЭНИН) Кафедра теоретической и промышленной теплотехники (ТПТ)
Այլ հեղինակներ: Nagornova T. A. Tatiana Aleksandrovna, Chernyshev V. S. Vladimir
Ամփոփում:Title screen
Is carried out the mathematical simulation of heat transfer processes in the small environment of vaporizer camera of heat pump (HP) when the source of low-potential energy is present. Are obtained the temperature distributions, which characterize thermal condition HP. Is carried out the comparative analysis of the results of mathematical simulation and experimental data from the work of heat-pumping installation in the conditions of relatively low (up to 4 °С) temperatures. In the experiments, the partial freezing around of the tubes of vaporizer is established. It is revealed, that the formation of the layer of ice on the surface of vaporizer leads to the temperature contrast by the volume of liquid in the camera and reduction in the effectiveness in the work of heat-pumping installation.
Լեզու:անգլերեն
Հրապարակվել է: 2015
Խորագրեր:
Առցանց հասանելիություն:http://dx.doi.org/10.1051/matecconf/20152301051
http://earchive.tpu.ru/handle/11683/15572
Ձևաչափ: Էլեկտրոնային Գրքի գլուխ
KOHA link:https://koha.lib.tpu.ru/cgi-bin/koha/opac-detail.pl?biblionumber=645256
Նկարագրություն
Ամփոփում:Title screen
Is carried out the mathematical simulation of heat transfer processes in the small environment of vaporizer camera of heat pump (HP) when the source of low-potential energy is present. Are obtained the temperature distributions, which characterize thermal condition HP. Is carried out the comparative analysis of the results of mathematical simulation and experimental data from the work of heat-pumping installation in the conditions of relatively low (up to 4 °С) temperatures. In the experiments, the partial freezing around of the tubes of vaporizer is established. It is revealed, that the formation of the layer of ice on the surface of vaporizer leads to the temperature contrast by the volume of liquid in the camera and reduction in the effectiveness in the work of heat-pumping installation.
DOI:10.1051/matecconf/20152301051